[PDF] 2013-02-02 Draft CSA B52-13 Safety Bulletin on Max Refrigerant





Previous PDF Next PDF





ABSA - Authority Having Jurisdiction for the CSA B52 Mechanical

Aug 31 2018 CSA B52 is referenced in both the Pressure Equipment Safety Regulation and the Alberta Building Code. This Information Bulletin provides ...



Refrigerants

Oct 15 2018 CSA B52 is the safety code for refrigeration and it relies heavily on ASHRAE 15 for technical content. • B52 currently allows up to 6.6lb of ANY ...



Authority Having Jurisdiction for the CSA B52 Mechanical

Nov 17 2017 CSA B52 is referenced in both the Pressure Equipment Safety Regulation and the Alberta Building Code. This Information Bulletin provides ...



DIRECTIVE

Mar 7 2008 CSA B52-05 Clause 6.10 (previously Clause 5.10 of CSA B52-99) requires the designer to consider the provision of an emergency discharge ...



Information Bulletin No. IB23-036 August 21 2023 NOTIFICATION

Aug 21 2023 The Mechanical refrigeration code (CSA B52) provides requirements for the design





Refrigerant Code References to Gas Detection (CSA and ASHRAE)

Refer to your local codes for specific requirements. CSA B52-05. 6.2.3 Refrigerant Vapour Detector. For all refrigerants except ammonia



A practical handbook for implementing CSA B52:18 Mechanical

Jan 20 2020 This document is provided by the Canadian Standards Association (operating as “CSA Group”) as a convenience only.



Norme CSA-B52:18

courant qu'une nouvelle édi- tion anglaise de la norme CSA. B52:18 a été publiée au prin- temps 2019. Néanmoins comme l'édi-.



B52 Mechanical Refrigeration Code

Canadian Standards Association (CSA) standards are developed through a consensus standards development process approved by the. Standards Council of Canada.



B52 Information Bulletin Use of Hydrocarbon Refrigerants

1 mars 2002 CSA Standard B52-99 Mechanical Refrigeration Code



2013-02-02 Draft CSA B52-13 Safety Bulletin on Max Refrigerant

12 déc. 2013 refrigerant quantities per occupied space as listed in Table 1 CSA B52-13 Mechanical Refrigeration Code for A1 and B1 refrigerants.



Information Bulletin No. IB18-019 August 31 2018 Authority Having

31 août 2018 The Mechanical refrigeration code (CSA B52) provides requirements for the design construction



Soirée conférence ASHRAE chapitre Montréal Réfrigération

24 janv. 2018 norme CSA B52. Présenté par : Myriam St-Georges ing. Bureau d'expertise et d'homologation en équipements sous pression. Janvier 2018.



Authority Having Jurisdiction for the CSA B52 Mechanical

17 nov. 2017 The Mechanical refrigeration code (CSA B52) provides requirements for the design construction





Refrigerants

15 oct. 2018 B52 specifically does NOT cover residential air conditioning but yet the standard is called on by CSA product standards for the refrigerant ...



Refrigeration System Review

with CSA B52-13 Mechanical Refrigeration Code. The system is a central plant design utilizing the refrigerant R-717 (ammonia). All major.



Appendix Y: CSA B52 Code Rules Relating to Emergency Discharge

INVESTIGATION REPORT. Ammonia Release October 17 2017. APPENDIX Y. Page 1 of 1 www.technicalsafetybc.ca. Appendix. Appendix Y: CSA B52 Code Rules Relating 

1

December 12, 2013

Safety Bulletin

Maximum Refrigerant Quantities per Occupied Space

Derivation of values for Table 1, CSA B52-13 for A1 and B1 Refrigerants

Introduction

This information bulletin serves to provide additional information with respect to the derivation of the

refrigerant quantities per occupied space as listed in Table 1, CSA B52-13 Mechanical Refrigeration Code

for A1 and B1 refrigerants.

Limiting the total quantity of refrigerant permitted in a specified occupied space is a significant health

and safety issue. Therefore the listed values are chosen to minimize negative effects (e.g. narcosis,

cardiac sensitization or insufficient oxygen to support life) for occupants in the event of refrigerant

leakage. These limiting values also have a significant influence on the determination of the overall

design of a refrigeration system and the associated space, and for this reason the calculation methodology of the values is further detailed herein under to assist Code users in their review and application of appropriate limits. Code users are also reminded that the maximum quantities of refrigerant per occupied space are subject to approval of the regulatory authority where the refrigeration system is to be installed.

Refrigerant Classifications and Quantities

To note, Table 1 of CSA B52-13 provides a list of some refrigerants, selected by their common usage in

installations in Canada. The Table is segregated by refrigerant classifications including, Groups A1, single

fluids and blends, A2, A3, B1 and B2. The refrigerant numbers and associated group numbers originate

from classifications as set forth by ASHRAE1. ASHRAE Standard 34-13, Safety Standard for Refrigerating Systems is recognized as establishing the latest and most complete information available for refrigerant technical data for North American

refrigeration standards. Designers are provided values as prescribed in Table 1, CSA B52-13, however in

a note to the Table it is identified that where conflict occurs with the ASHRAE standard, the latter prevails.

RCL (Refrigeration Concentration Limit)

There are three methods of determining the RCL (Refrigeration Concentration Limit) for a given refrigerant;

1 ASHRAE is the American Society of Heating, Refrigerating and Air-Conditioning Engineers

2 i. Acute Toxicity Exposure Limit (ATEL) as defined in ASHRAE Standard 34-13 section 7.1.1, ii. Oxygen Deprivation Limit (ODL) as defined in ASHRAE Standard 34-13 Section 7.1.2, and iii. Flammable Concentration Limit (FCL) as defined in ASHRAE Standard 34-13 Section 7.1.3

The RCL to be used for an application is the lowest value determined from the three methods (Note that

ODL limits are related to elevation above sea level. It is therefore possible that refrigerants may have an

RCL related by ATEL at sea level, and an RCL related by ODL at higher elevations. R-407C is an example).

For illustration, concentration limits from CSA B52-13 for a few common refrigerants are provided in Figure A. For these same refrigerants, the corresponding RCL values at sea level and the ODL values from ASHRAE Standard 34-13 are provided in Figures B, C and D. To note, flammability is not a consideration for these examples.

Calculation Methodology for CSA B52-13, Table 1

The RCL values provided for in CSA B52-13 Table 1 are derived from both calculated and tabular values

for ODL at elevations above 1500m and ATEL at sea level from ASHRAE 34-13. ODL

All refrigerants heavier than air have a risk of asphyxiation. The molecular mass of air is 28.97 g/mol.

The RCL defined by ODL is based on the altitude of the application as defined in ASHRAE 34-13 Clause

7.1.2 and is provided in three altitude categories (refer to Figures B-D):

a. An RCL value of 140,000 ppm v/v shall be used for all refrigerants heavier than air at an altitude

below 1000 m. For example, according to this calculation for this altitude, R-410A has an allowable concentration of 0.4163 kg/m3.

b. An RCL value of 112,000 ppm v/v shall be used for all refrigerants heavier than air at an altitude

between 1000 m and 1500 m. For example, according to this calculation for this altitude, R-410A has an allowable concentration of 0.3331 kg/m3. c. An RCL value of 69,100 ppm v/v shall be used for all refrigerants heavier than air at an altitude greater than 1500 m. For example, according to this calculation for this altitude, R-410A has an allowable concentration of 0.2055 kg/m3.

RCL at Sea Level

The RCL sea level values2 are presented per ASHRAE Standard 34-13, Tables 4-1 and 4-2 in ppm v/v. The

RCL is converted into a mass per unit volume using the calculation method detailed in section 7.4.1 of

ASHRAE Standard 34-13 based upon the molecular mass of the refrigerant. The resultant RCLM is then the basis for concentration limit calculations expressed in kg/m3 (refer to Figures B-D).

2 These values are the lowest value as determined by ATEL and ODL. FCL is not a factor for the examples

presented. 3 For example, according to this calculation, the R-410A has an RCL at sea level of 140,000 ppm v/v and a resulting allowable concentration at sea level of 0.4163 kg/m3. RCL at sea level with Adjustment Based on Altitude The RCLM for refrigerants limited by Oxygen Deprivation must be adjusted based upon altitude of an application when expressed as mass per unit volume3, g/m3. It shall be adjusted according to ASHRAE

Standard 34-13, section 7.4.2 and is represented with rcla. It must be noted that the same evaluation at

a different altitude may yield different results. Figures B, C and D provide examples at three different

specified altitudes, 105m, 250m and 1100m with bolded values indicating where the RCL is selected, that is either RCL at sea level adjusted for height, or the ODL value at the corresponding altitude threshold. For example, the RCL value for R-410A in Figure D at an elevation of 1100m is determined by the ODL value at an altitude between 1000m and 1500m, 0.3331 kg/m3.

RCL Values in CSA B52-13, Table 1

The maximum refrigerant quantities per occupied space presented in CSA B52-13 for A1 and B1 refrigerants are based on the lesser of two values, RCL at sea level or ODL above 1500m altitude as determined from ASHRAE Standard 34-13. Therefore the ODL may be adjusted to match application specific altitudes. It is not mandatory to use the values corresponding to altitudes above 1500m. For example, the R-410A RCL (kg/m3), refer to Figures A through D:

CSA B52-13

Sea level 105m 250m 1000-1500m Greater than 1500m

0.2055 0. 4163 0.4128 0.4081 0.3331 0.2055

Figure A: Refrigeration Concentration Limits, CSA B52-13

CSA B52-13

Based on the lower value of either

ASHRAE 34-13 values for

ATEL at Sea Level or

ODL Above 1500 m Altitude

Refrigerant kg/m3 Vol. % lb/1000ft3

R-134a 0.2089 5.00 13.02

R-404A 0.2762 6.91 17.22

R-407C 0.2440 6.91 15.21

R-410A 0.2055 6.91 12.81

R-507A 0.2799 6.91 17.45

R-744 0.0721 4.00 4.49

3 The RCL is not adjusted when expressed as a volumetric ratio, ppm.

4 Figure B: Refrigeration Concentration Limits at 105m Elevation (bold values identify allowable concentrations)

Altitude

Adjustment for

RCL (2)

Example @

ODL (Oxygen Deprivation Limit) (3)

Refrigerant

RCL at Sea Level (1) 105 meters Altitude less than 1000m Altitude between 1000m and 1500m

Altitude greater than

1500m
RCL ppm v/v RCLM (g/m3) kg/m3 rcla (g/m3) kg/m3

RCL0 to

1000
ppm v/v RCLM (g/m3) kg/m3

RCL1000

to 1500 ppm v/v RCLM (g/m3) kg/m3 RCL1500+ ppm v/v RCLM (g/m3) kg/m3

R-134a 50,000 208.8960 0.2089 207.1544 0.2072 140,000 584.9088 0.5849 112,000 467.9270 0.4679 69,100 288.6943 0.2887

R-404A 130,000 519.7005 0.5197 515.3677 0.5154 140,000 559.6774 0.5597 112,000 447.7420 0.4477 69,100 276.2408 0.2762

R-407C 81,000 285.9909 0.2860 283.6066 0.2836 140,000 494.3053 0.4943 112,000 395.4442 0.3954 69,100 243.9750 0.2440

R-410A 140,000 416.3174 0.4163 412.8466 0.4128 140,000 416.3174 0.4163 112,000 333.0540 0.3331 69,100 205.4824 0.2055

R-507A 130,000 526.6227 0.5266 522.2323 0.5222 140,000 567.1322 0.5671 112,000 453.7057 0.4537 69,100 279.9202 0.2799

R-744 40,000 72.0896 0.0721 71.4886 0.0715 140,000 252.3136 0.2523 112,000 201.8509 0.2019 69,100 124.5348 0.1245

Note: The values in the table above are sourced or calculated from sections of ASHRAE Standard 34-13 as indicated:

(1) Tables 4-1 and 4.2; (2) Section 7.4.2; and (3) Section 7.1.2 5 Figure C: Refrigeration Concentration Limits at 250m Elevation (bold values identify allowable concentrations)

Altitude

Adjustment for

RCL (2)

Example @

ODL (Oxygen Deprivation Limit) (3)

Refrigerant

RCL at Sea Level (1) 250 meters Altitude less than 1000m Altitude between

1000m and 1500m Altitude greater than 1500m

RCL ppm v/v RCLM (g/m3) kg/m3 rcla kg/m3 RCL0 to 1000
RCLM (g/m3) kg/m3 RCL100

0 to 1500 RCLM kg/m3 RCL1500+ RCLM

(g/m3) kg/m3

R-134a 50,000 208.8960 0.2089 204.7494 0.2047 140,000 584.9088 0.5849 112,000 467.9270 0.4679 69,100 288.6943 0.2887

R-404A 130,000 519.7005 0.5197 509.3844 0.5094 140,000 559.6774 0.5597 112,000 447.7420 0.4477 69,100 276.2408 0.2762

R-407C 81,000 285.9909 0.2860 280.3140 0.2803 140,000 494.3053 0.4943 112,000 395.4442 0.3954 69,100 243.9750 0.2440

R-410A 140,000 416.3174 0.4163 408.0535 0.4081 140,000 416.3174 0.4163 112,000 333.0540 0.3331 69,100 205.4824 0.2055

R-507A 130,000 526.6227 0.5266 516.1693 0.5162 140,000 567.1322 0.5671 112,000 453.7057 0.4537 69,100 279.9202 0.2799

R-744 40,000 72.0896 0.0721 70.6586 0.0707 140,000 252.3136 0.2523 112,000 201.8509 0.2019 69,100 124.5348 0.1245

Note: The values in the table above are sourced or calculated from sections of ASHRAE Standard 34-13 as indicated:

(1) Tables 4-1 and 4.2; (2) Section 7.4.2; and (3) Section 7.1.2 6 Figure D: Refrigeration Concentration Limits at 1100m Elevation (bold values identify allowable concentrations)

RCLa , Altitude

Adjustment for

RCL (2)

Example @

ODL (Oxygen Deprivation Limit) (3)

Refrigerant

RCL at Sea Level (1) 1100 meters Altitude less than 1000m Altitude between 1000m and 1500m

Altitude greater than

1500m
RCL ppm v/v RCLM (g/m3) kg/m3 rcla kg/m3 RCL0 to 1000
RCLM (g/m3) kg/m3 RCL1000 to 1500 RCLM kg/m3 RCL1500+ RCLM (g/m3) kg/m3

R-134a 50,000 208.8960 0.2089 190.6510 0.1907 140,000 584.9088 0.5849 112,000 467.9270 0.4679 69,100 288.6943 0.2887

R-404A 130,000 519.7005 0.5197 474.3098 0.4743 140,000 559.6774 0.5597 112,000 447.7420 0.4477 69,100 276.2408 0.2762

R-407C 81,000 285.9909 0.2860 261.0125 0.2610 140,000 494.3053 0.4943 112,000 395.4442 0.3954 69,100 243.9750 0.2440

R-410A 140,000 416.3174 0.4163 379.9563 0.3800 140,000 416.3174 0.4163 112,000 333.0540 0.3331 69,100 205.4824 0.2055

R-507A 130,000 526.6227 0.5266 480.6275 0.4806 140,000 567.1322 0.5671 112,000 453.7057 0.4537 69,100 279.9202 0.2799

R-744 40,000 72.0896 0.0721 65.7933 0.0658 140,000 252.3136 0.2523 112,000 201.8509 0.2019 69,100 124.5348 0.1245

Note: The values in the table above are sourced or calculated from sections of ASHRAE Standard 34-13 as indicated:

(1) Tables 4-1 and 4.2; (2) Section 7.4.2; and (3) Section 7.1.2 7 This bulletin was published on behalf of the CSA B52 Technical Committee on Mechanical Refrigeration Code. For more information, please contact your local regulatory authority or:

Oreste Simonetta

Project Manager

Canadian Standards Association

Tel (416) 747-2709

Email: oreste.simonetta@csagroup.org

quotesdbs_dbs50.pdfusesText_50
[PDF] csc cn study china newsdetail fr

[PDF] csdge karate 2016

[PDF] csf ofppt manuel des procédures

[PDF] csf ofppt org ma

[PDF] csfmg grombalia grombalia

[PDF] csss de gatineau emploi

[PDF] csss gatineau ressources humaines

[PDF] csst ajustement poste de travail

[PDF] ctes

[PDF] cti

[PDF] cuadro comparativo de la constitucion de 1998 y 2008 del ecuador

[PDF] cuadro comparativo decreto 1443 y 1072

[PDF] cuadro comparativo resolucion 1016 de 1989 y decreto 1443 de 2014

[PDF] cual es el decreto unico reglamentario de las niif

[PDF] cual es el objetivo de las meditaciones metafisicas