974 devices are controllers with 2 relay outputs, 2 temperature sensors ( regulation and evaporator),
Previous PDF | Next PDF |
IDPLUS - Eliwell
CE UTILISATEUR IDPLUS 971/974 (TOUCHES ET LEDS)
ID 974 fra - Eliwell
pdf › ID 97 PDF
ID 974 fra - Frigoristesfr
T UTILISATION DES MENUS La programmation de l'instrument est organisé par un menu
Contrôleurs électroniques pour unités réfrigérantes - Doregrill
s EW Plus 971/974: La signalisation d'alarme pour sonde 2 défectueuse ( Pb2) ELIWELL CONTROLS SRL décline toute responsabilité en cas de dommages dérivant de:
ID 974 NTC(PTC) - Delco Controls AG
mation « Set » (POINT DE CONSIGNE/Température d'arrêt du compresseur): Appuyer, en la
IDPLUS
nic controllers for refrigeration units IDPLUS 902/961/971/974 GB ELIWELL CONTROLS SRL declines any liability for
Eliwell Controller 974 - Axair Refrigeration
974 devices are controllers with 2 relay outputs, 2 temperature sensors ( regulation and evaporator),
[PDF] eliwell regulateur
[PDF] elkhadra bac
[PDF] elle voulait juste s'amuser avec moi musique
[PDF] elle voulait s'excuser moi je ne voulais pas musique
[PDF] elliott spencer (m. 2015)
[PDF] élongation traduction
[PDF] em strasbourg classement
[PDF] email in english example business
[PDF] embarazo definicion pdf
[PDF] embarazo normal pdf
[PDF] embarazo pdf libro
[PDF] embarazo pdf oms
[PDF] embryo
[PDF] embryologie 150 qcm corrigés
Controller 974
Technical Information
www.axair-refrigeration.co.uk01782 618 444
IDPlus
974 devices are controllers with 2 relay outputs, 2 temperature sensors (regulation
and evaporator), a multifunctional Digital/Temperature input and a digital input.IDPlus 974 User Interface
IDPlus 974
The relay output 2 ND 3 can be used to control:STANDBY (ESC)
Press and releaseReturns to the previous menu levelConfirms parameter valuePress for at least 5 secActivates the Standby function(when outside the menus)
UP Press and releaseScroll menu itemsIncreases valuesPress for at least 5 secActivates the Manual Defrost function
DOWN Press and releaseScroll menu itemsDecrease valuesPress for at least 5 sec Function can be configured by the user
SET (ENTER)
Press and releaseDisplays alarms (if active)Opens Machine Status menuPress for at least 5 secOpens Programming menuConfirm commands
KEYS set setReduced SET / Economy LED
Flashing: economy Setpoint active
Quic k flashing: access to level2 parametersOff: otherwise
Compressor LED
Per manently on: compressor activeFlashing:a delay, a protection or a locked start-upOff: otherwiseAlarm LED
Per manently on: alarm activeFlashing: alarm acknowledged
Off: otherwise
°C LED
Per manently on: °C setting (dro =0)Off: otherwise
°F LED
Per manently on: °F setting (dro =1)Off: otherwise
LEDsDefrost LED
Per manently on: defrost activeFlashing: manual or D.I. activation
Off: otherwise
Fans LED
Per manently on: fans activeOff: otherwise
Aux LED
Per manently on: Aux output activeFlashing:manual or D.I. activation of
DeepCooling
* When switched on, the device performs a Lamp Test; the display and LEDs will flash for several seconds to check that they
all function correctly.* To activate the LOC function: - enter the "Basic Commands" menu by pressing the key set press keys and within 2 seconds. Ifthe LOC function is Active and you try to enter the "Programming" menu, the text LOC appears. If this happens, the
parametersare still displayed but cannot be edited. To disable the keypad lock, repeat the aforementioned procedure.
compressor- defrost heating elements- evaporator fans- AUX output- temperature alarm- Standby The second probe can be used to control the defrost cycle and the evaporator fans. TheDigital inputs (D.I.1 and D.I.2) can be used for:
Energy saving- Defrost activation
AUX management- door switch- Standby- external alarm- Deep Cooling- pressure switchHACCP alarms
sales@axair-refrigeration.co.ukController 974
Technical Information
www.axair-refrigeration.co.uk01782 618 444
sales@axair-refrigeration.co.ukAP3AP1AP2
AP4Evaporator
T.E.V.Pb1
Ambient
ValveCompressor
Pb2Evaporator
T.E.V.Pb1
Ambient
ValveCompressor
Evaporator
T.E.V.Pb1
Ambient
Valve D.I.1Compressor
Pb2Evaporator
T.E.V.Pb1
Ambient
ValveCompressor
External Alarm
InternalBuzzer
Ambient= AmbientValve= Valve
Evaporator= EvaporatorCompressor= Compressor
Internal Buzzer= Internal BuzzerT.E.V.= Thermostatic Expansion ValveExternal
Alarm= External Alarm
TABLEOF USER MENU PARAMETERS (IDPlus 974)
Par.DESCRIPTIONRANGEAP1AP2AP3AP4M.U.SetTemperature control SetpointLSE ... HSE0,00,00,00,0°C/°FDifCompressor relay activation differential0,1 ... 30,02,02,02,02,0°C/°FHseMaximum value that can be assigned to the SetpointLSE ... 30299,099,099,099,0°C/°FLseMinimum value that can be assigned to the Setpoint-58.0 ... HSE-50,0-50,0-50,0-50,0°C/°FDtyType of defrost0/1/2001numDitInterval between the start of two consecutive defrost cycles0 ... 2506666hoursDetDefrost timeout1 ... 25030303030minDstEnd defrost temperature-50,0 ... 1508,08,08,08,0°C/°FFstFans stop temperature-58,0 ... 30250,050,050,050,0°C/°FFdtFan activation delay after a defrost cycle0 ... 2500000minDtCoil drainage time0 ... 2500000minDfdTo select or exclude the fans (it depends on FCO parameter)n/yyyyyminHalMaximum temperature alarmLAL ... 15050,050,050,050,0°C/°FLalMinimum temperature alarm-50.0 ... HAL-50,0-50,0-50,0-50,0°C/°FLocBasic commands modification lockn/ynnnnflagPs1Password 1 for access to QUICK menu parameters0 ... 2500000numCa1Calibration1. Value to be added to the value read by probe 1-12,0 ... 12,00,00,00,00,0°C/°FCa2Calibration2. Value to be added to the value read by probe 2-12,0 ... 12,00,00,00,00,0°C/°FCa3Calibration3. Value to be
added to the value read by probe 3-12,0 ... 12,00,00,00,0°C/°FDdlDisplay mode during defrost0/1/20000numLddDisplay lock disabling timeout. 0 = function disabled0 ... 25530303030minShhMaximum HACCP alarm signals threshold-55,0 ... 15010,0°C/°FSlhMinimum HACCP alarm signals threshold-55,0 ... 150-10,0°C/°FDraMinimum time spent in critical range before alarm occurs0 ... 9910minDrhHACCP alarm reset time after last reset0 ... 25024hoursH50enable HACCP and alarm relay functions0/1/21numH51HACCP alarm exclusion time0 ... 2500minH42Evaporator probe present. n = not present; y = presentn/yyyyyflagH43Probe 3 presentn/ynynnflagRelfirmware rELease. Reserved: read-only parameter//////TabtAble of parameters. Reserved: read-only parameter//////
Notes: * The USER menu parameters also include: PA2, which can be used to access the Installer menu ** To reset the HACCP alarms, use the rES function in the FnC folder for Installer parameters
Controller 974
Technical Information
www.axair-refrigeration.co.uk01782 618 444
sales@axair-refrigeration.co.uk PAR .DESCRIPTIONRANGEAP1AP2AP3AP4M.U. SetTemperature control Setpoint.LSE ... HSE0,00,00,00,0°C/°F COMPRESSOR ("CP" folder)
Di fdifferential. Compressor relay activation differential.0,1...30,02,02,02,02,0°C/°F HS EHigher Set. Maximum value that can be assigned to the Setpoint.LSE...30299,099,099,099,0°C/°F LseLower SEt. Minimum value that can be assigned to the Setpoint.-58,0...HSE-50,0-50,0-50,0-50,0°C/°F
Os pTemperature value to be added to the Setpoint if reduced set enabled(Economy function).-30,0...30,03,00,00,03,0°C/°F
HcControl mode. C (0) = Cold; H (1) = Hot.C/HCCCCflag On t Controller on time for faulty probe.If Ont = 1 and OFt = 0, the compressor remains on;if Ont=1 and OFt>0 it runs in duty cycle mode.0 ... 2500000min
Of t Controller off time for faulty probe.If OFt = 1 and Ont = 0, the controller remains off;if OFt = 1 and Ont>0
, it operates in duty cycle mode.0 ... 2501111min Do nCompressor relay activation delay after request.0 ... 2500000secs Do fDelay after switching off and subsequent activation.0 ... 2500000min Db iDelay between two consecutive compressor activations.0 ... 2500000min Od o(!) Delay in activating outputs after the instrument is switched on or after a power failure. 0 = not active.0 ... 2500000min DcsDeep Cooling cycle Setpoint.-58,0...3020,00,00,00,0°C/°F Td cDeep Cooling cycle duration.0 ... 2550000min DccDefrost activation delay after a Deep Cooling cycle.0 ... 2550000min DE FR OST ("def" folder)
DtyType of defrost. 0 = electrical defrost;1 = reverse cycle defrost; 2 = defrost independent of compressor.0/1/20001num
Di tInterval between the start of two consecutive defrost cycles.0 ... 2506666hours Dc t Selec tion of count mode for the defrost interval.0 = compressor running time; 1 = appliance running time;2 = A defrost cycle is run at each compressor stop.0/1/21111num
TABLE OF INSTALLER MENU PARAMETERS (IDPlus 974)
PAR.DESCRIPTIONRANGEAP1AP2AP3AP4M.U.
Do hDelay for start of first defrost after request.0 ... 590000min De tDefrost timeout; determines the maximum defrost duration.1 ... 25030303030min Ds tDefrost end temperature - determined by probe Pb2.-50,0...1508,08,08,050,0°C/°F Dp o Determines whether the instrument must enter defrost mode at start-up.n (0) = no; y (1) = yes.n/ynnnnflag
FANS ("Fan" folder)
FstFans stop temperature.-58,0...30250,050,050,050,0°C/°F FadFan activation differential.1,0 ... 50,02,02,02,02,0°C/°F FdtFan activation delay after a defrost cycle.0 ... 2500000minDtCoil drainage time.0 ... 2500000min
Df d Allo ws evaporator fan exclusion to be selected or not selected during defrosting. n (0) = no (it depends on FCO parameter); y (1) = yes (fans excluded).n/yyyyyflagFcoSelects or deselects fan deactivation at compressor OFF.0 = fans off; 1 = fans active; 2 = duty cycle0/1/20000num
FonFans ON time in day duty cycle.0 ... 990000min
FofFans OFF time in day duty cycle.0 ... 990000min FnnFans ON time in night duty cycle.0 ... 990000min FnfFans OFF time in night duty cycle.0 ... 990000min EsfNight mode activation. n (0) = no; y (1) = yes.n/ynnnnflagALARMS
("AL" folder) At t Can be used to select absolute (Att=0) or relative (Att=1) values for HAL and LAL para meters.0/10000num
Af dAlarm differential.1,0 ... 50,02,02,02,02,0°C/°F Hal Maxi mum temperature alarm.LAL...30250,050,050,050,0°C/°F LalMinimum temperature alarm.-58,0...HAL-50,0-50,0-50,0-50,0°C/°F Pa oAlarm exclusion time after re-activation following a power failure.0 ... 100000hours Da oTemperature alarm exclusion time after defrost.0 ... 9990000min Oa oAlarm signalling delay after disabling of digital input.0 ... 100000hours TdoDelay in door open alarm activation.0 ... 2500000min TaoTime delay for temperature alarm indication.0 ... 2500000minController 974
Technical Information
www.axair-refrigeration.co.uk01782 618 444
sales@axair-refrigeration.co.uk PAR .DESCRIPTIONRANGEAP1AP2AP3AP4M.U. Da tAlarm signalling end of defrost due to timeout. n (0) = no; y (1) = yes.n/ynnnnflag RloExternal alarm locks controllers. n (0) = does not lock; y (1) = locks.n/ynnnnflag Sa3Probe 3 alarm Setpoint.-58,0...3020,00,00,00,0°C/°F
Da3Probe 3 alarm differential.1,0 ... 50,01,01,01,01,0°C/°F
LIGHTS & DIGITAL INPUTS ("Lit" folder)
Do dDigital
input for switching off utilities. 0=disabled;1=disables fans; 2=disables the compressor; 3=disables fans and compressor.
0/1/2/30000num
Da dActivation delay for digital input.0 ... 2550000min Dc oCompressor deactivation delay after door opened.0 ... 2551111min Au pAux output activation when door opened. n (0) = not linked; y (1) = linked.n/ynnynflag PRESSURE SWITCH ("Pre"
folder) Pe nNumber of errors allowed per maximum/minimum pressure switch input.0 ... 150000num PeiMinimum/maximum pressure switch error count interval.1 ... 991111min PetDelay in activating compressor after pressure switch deactivation.0 ... 2550000minCOMMUN
ICATION ("Add" folder)
PtsCommunication protocol selection. t (0) = Televis; d (1) = Modbus.t/dttttflag DeaIndex of the device inside the family (valid values from 0 to 14).0 ... 140000num Fa aDevice family (valid values from 0 to 14).0 ... 140000num PtyModbus parity bit. n (0) = none; E (1) = even; o (2) = odd.n/E/onnnnnum StpModbus stop bit. 1b (0) = 1 bit; 2b (1) = 2 bit.1b/2b1b1b1b1bflagDISPLA
Y ("dis" folder)
Lo cBasic commands modification lock. It
is still possible to enter parameter programming mode and modify them. n (0) = no; y (1) = yes.n/ynnnnflag
Ps1PAssword1: if PSĿ0 is the access key to User parameters.0 ... 2500000num
Ps2PAssword2: if PSĿ0 is the access key to Installer parameters.0 ... 25015151515num
Nd tDisplay with decimal point. n (0) = no; y (1) = yes.n/yyyyyflag Ca1Calibration 1. Temperature value to be added to the Pb1 value.-12,0...+12,00,00,00,00,0°C/°F
Ca2Calibration 2. Temperature value to be added to the Pb2 value.-12,0...+12,00,00,00,00,0°C/°F
Ca3Calibration 3. Temperature value to be added to the Pb3 value.-12,0...+12,00,00,00,00,0°C/°F
PAR.DESCRIPTIONRANGEAP1AP2AP3AP4M.U.
Dd l Di splay mode during defrost. 0 = display the temperature recorded by Pb1;1 = lock recorded value of Pb1 at defrost start; 2 = display the "dEF" label.
0/1/20000num
LddTimeout value for display unlock - dEF label.0 ... 25530303030min Dr o Sele ct the unit of measurement used when displaying the temperature recorded by the probes. (0 = °C, 1 = °F).NOTE: switching between °C and °F or viceversa DOES NOT modify the Set, dif values, etc. (e.g. Setpoint=10°C becomes 10°F).0/10000flag
Dd d Sele cts the type of value to display.0 = Setpoint; 1 = probe Pb1; 2 = probe Pb2; 3 = probe Pb3.0/1/2/31111num
HACCP ("HCP" folder)
Sh hMaximum HACCP alarm signals threshold.-55,0...15001000°C/°F Sl hMini mum HACCP alarm signals threshold.-55,0...1500-1000°C/°F Dr a Mini mum time spent in critical range for the event to be recorded. After this a HACCP alarm will be triggered and logged.0 ... 9901000min Dr hHACCP alarm reset time after last reset.0 ... 25002400hours H5 0 Enable HACCP and alarm relay functions. 0= HACCP alarms NOT enabled;1 = HACCP alarms enabled and alarm relay NOT enabled;
2 = HACCP alarms enabled and alarm relay enabled.
0/1/20100num
H51HACCP alarm exclusion time.0 ... 2500000min
CONFIGURATION ("CnF" folder) If one or more parameters present in this forder are changed, the controller MUST be powered-off
and than powered-on. H00 (!)Probe type selection. 0 = PTC; 1 = NTC; 2 = PT1000.0/1/21111num H1 1