Pressure transmitter PASCAL CV









Pressure transmitter PASCAL CV4 - for diaphragm seal operation

DB_D4-016-7_en_12.01 2020-12 Pressure transmitter PASCAL CV4. Page 2/10 0.05 bar. 2 bar. 3 bar rel. 30 mbar abs. -1...4 bar rel. 0.2 bar. 5 bar.
Labom PRESSURE TRANSMITTER PASCAL Series CV datasheet


Pressure transmitter/Pressure switch PASCAL CS

0…1 bar to 0…6 bar abs. The pressure transmitter/pressure switch PASCAL CS is ... 10 bar. A1054. 0...16 bar. 10 bar. A1055. 0...2
Datasheet PASCAL CS


Pressure transmitter PASCAL CV4 - with threaded connection Type

0…1 bar *. 0.05 bar. 2 bar. 3 bar. 100 mbar abs. Piezoresistive. 0…4 bar *. 0.2 bar. 5 bar. 10 bar. 100 mbar abs. 0…16 bar *. 0.8 bar. 17 bar. 60 bar.
D CV EN


Pressure transmitter PASCAL CV4 - for diaphragm seal operation

DB_D4-016-7_en_13.00 2022-04 Pressure transmitter PASCAL CV4. Page 2/8. Technical data 200 bar. 100 mbar abs. -0.25…0.25 bar. 0.0125 bar. 05 bar. 1 bar.
D CV EN





Differential pressure transmitter PASCAL Ci4 Delta P - for

5 bar. 75 bar. 1 bar. 0.01 bar. 2 bar. 20 bar. 10 bar. 75 bar. 4 bar. 0.04 bar. 5 bar. 50 bar. 25 bar. 75 bar. 16 bar. 0.16 bar. 17 bar. 100 bar. 75 bar.
datablad remote seal


PA Bar Admission Rules

Jan 4 2022 "Pa.B.A.R.". Adopted July 1
rules


Pressure transmitter PASCAL CV

measuring spans 1 min. span max. span overload limits vakuum tight at < 50 °C 2. 0.4 bar. 5:1. -0.4…0.4 bar. 80 mbar. 0.8 bar. 1 bar. 400 mbar abs. 1 bar.
datablad


Pressure transmitter PASCAL Ci4 - for diaphragm seal operation

100 bar. -. 100 mbar abs. -025…0
D CI EN





BaseControl®

Safe operation with compressed gases up to 230 bar Acetylene 25/15 bar. - Propane 25/4 bar ... PA. CR. Inlet/Outlet connection. Gas specific connection.
BASECONTROL DIN EN


Pressure transmitter PASCAL Ci4 - with threaded connection Type

0…1 bar *. 0.01 bar. 2 bar. 3 bar. -. 100 mbar abs. Piezoresistive. 0…4 bar *. 0.04 bar. 5 bar. 10 bar. -. 100 mbar abs. 0…16 bar *. 0.16 bar. 17 bar.
D CI EN


210465 Pressure transmitter PASCAL CV

Pressure transmitter PASCAL CV

for general applications,Type series CV310.

Data sheet D4-017-1 Rev. 1G5

Application area

Features

mounted diaphragm

Output signal:

- 4...20 mA - HART® protocol (rev. 6), option - PROFIBUS PA, option - Multifunctional display with 5-segment digital display and bar graph - Switching module with 2 flating channels, maximum

0.5 A switching current, electrically isolated at all

sides, without additional auxiliary power bration "plug and measure" cell directly aerated

Options

- Explosion protection for gases and dust - Certificate of measuring equipment for Russian

Federation

- Material certificate as per EN 10204-3.1 - Calibration certificate as per EN 10204-3.1 - Classification per SIL2

Application

The modular pressure transmitter PASCAL CV is suited for measuring the relative and absolute pressures of gases, vapors and liquids.

PASCAL CV - the modular pressure transmitter

Data sheet D4-017-1 Rev. 1G5

Technical data

Measuring ranges

nominal range Turndown measuring ranges measuring spans 1 min. span max. span overload limits vakuum tight at < 50 °C 2

0.4 bar

5:1 -0.4...0.4 bar 80 mbar 0.8 bar 1 bar 400 mbar abs

1 bar -1...1 bar 0.2 bar 2 bar 3 bar 40 mbar abs

4 bar -1...4 bar 0.8 bar 5 bar 10 bar 20 mbar abs

16 bar -1...16 bar 3.2 bar 17 bar 60 bar 20 mbar abs

40 bar -1...40 bar 8 bar 41 bar 100 bar 20 mbar abs

100 bar -1...100 bar 20 bar 101 bar 200 bar 20 mbar abs

400 bar -1...400 bar 80 bar 401 bar 600 bar -

4 bar abs 0...4 bar abs 0.8 bar abs 4 bar abs 10 bar abs 20 mbar abs

16 bar abs 0...16 bar abs 3.2 bar abs 16 bar abs 60 bar abs 20 mbar abs

1

Long term vacuum measurements at relative measuring ranges may cause changes in the properties of the measurement device.

Vacuum-proof designs are available upon request.

2 calibrated measuring span for devices with PROFIBUS PA basic module.

Constructional design / case

Design: Hygienic case design with screw cap,

material: st. steel mat.no. 1.4301 (304)

Construction: Two-chamber system, minimum case

volume, excellent moisture and condensate protection

Degree of

Pressure

compensation: PTFE filter system

Window: Non splintering plastic: Makrolon

El. connection: Screw terminal 1 mm

2 material: PA

Further cable glands upon request.

Climatic

category: EN 60721 3-4, 4K4H

Weight: standard device with G1/2 without

function modules approx. 0.65 kg case design:

Process connection

Variants /

material: See order code

Material wetted parts

Sensor : Piezoresistive Thin film

Sensor

diaphragm: 1.4404/1.4435 (316L) 1.4542 (630)

Socket: 1.4404/1.4435

(316L) 1.4301/1.4404 (304/316L)

Gasket: EPDM-FDA listed

Measuring system

Sensor: Piezoresistive Thin film

Sensor filling: Synthetic oil, free of

silicone FD1, FDA listed without

Accuracy

General:

Limit point

setting: per DIN 16086

Reference

conditions: per EN 60770-1

Linearity

errors: 0.15 % of span

TD 5:1 no modification

Hysteresis: 0.05 % of nominal range

Repeatability: 0.05 % of nominal range

Calibration

position: Vertical mounting position

Influence of

mounting position: 3.5 mbar

Data sheet D4-017-1 Rev. 1G5

Long-term drift:

(EN 60770-1) 0.1 % / year of nominal range

Temperature

effect: Case:

Lower range value / upper range value

Range 0...60 °C:

± 0.15 % / 10K of nominal range

Range < 0 °C, > 60 °C:

± 0.2 % / 10K of nominal range

Output

General:

Delay time: approx. 160 ms

Measuring cycle: 6 measurements / second

Measuring range

setting: Turndown 5:1

Basic module: 4...20 mA

Signal: 4...20 mA, 2-wire

Current range: 3.8...20.8 mA

Current limitation: approx. 22 mA

Alarm state: < 3.6 mA, optional > 21 mA

Damping: 0...120 seconds

Load R

B : R B (U V -12V DC)/0,022A [Ohm] U V = supply voltage

Basic module: PROFIBUS PA

Signal: digital per IEC 61158-2

Protocol: EN 50170-PROFIBUS PA, Profile 3.0

Sensor address: 0...126 (126 = factory setting)

Power consumption: constantly 11 mA

Fault current

I FDE

Pressure transmitter PASCAL CV

for general applications,Type series CV310.

Data sheet D4-017-1 Rev. 1G5

Application area

Features

mounted diaphragm

Output signal:

- 4...20 mA - HART® protocol (rev. 6), option - PROFIBUS PA, option - Multifunctional display with 5-segment digital display and bar graph - Switching module with 2 flating channels, maximum

0.5 A switching current, electrically isolated at all

sides, without additional auxiliary power bration "plug and measure" cell directly aerated

Options

- Explosion protection for gases and dust - Certificate of measuring equipment for Russian

Federation

- Material certificate as per EN 10204-3.1 - Calibration certificate as per EN 10204-3.1 - Classification per SIL2

Application

The modular pressure transmitter PASCAL CV is suited for measuring the relative and absolute pressures of gases, vapors and liquids.

PASCAL CV - the modular pressure transmitter

Data sheet D4-017-1 Rev. 1G5

Technical data

Measuring ranges

nominal range Turndown measuring ranges measuring spans 1 min. span max. span overload limits vakuum tight at < 50 °C 2

0.4 bar

5:1 -0.4...0.4 bar 80 mbar 0.8 bar 1 bar 400 mbar abs

1 bar -1...1 bar 0.2 bar 2 bar 3 bar 40 mbar abs

4 bar -1...4 bar 0.8 bar 5 bar 10 bar 20 mbar abs

16 bar -1...16 bar 3.2 bar 17 bar 60 bar 20 mbar abs

40 bar -1...40 bar 8 bar 41 bar 100 bar 20 mbar abs

100 bar -1...100 bar 20 bar 101 bar 200 bar 20 mbar abs

400 bar -1...400 bar 80 bar 401 bar 600 bar -

4 bar abs 0...4 bar abs 0.8 bar abs 4 bar abs 10 bar abs 20 mbar abs

16 bar abs 0...16 bar abs 3.2 bar abs 16 bar abs 60 bar abs 20 mbar abs

1

Long term vacuum measurements at relative measuring ranges may cause changes in the properties of the measurement device.

Vacuum-proof designs are available upon request.

2 calibrated measuring span for devices with PROFIBUS PA basic module.

Constructional design / case

Design: Hygienic case design with screw cap,

material: st. steel mat.no. 1.4301 (304)

Construction: Two-chamber system, minimum case

volume, excellent moisture and condensate protection

Degree of

Pressure

compensation: PTFE filter system

Window: Non splintering plastic: Makrolon

El. connection: Screw terminal 1 mm

2 material: PA

Further cable glands upon request.

Climatic

category: EN 60721 3-4, 4K4H

Weight: standard device with G1/2 without

function modules approx. 0.65 kg case design:

Process connection

Variants /

material: See order code

Material wetted parts

Sensor : Piezoresistive Thin film

Sensor

diaphragm: 1.4404/1.4435 (316L) 1.4542 (630)

Socket: 1.4404/1.4435

(316L) 1.4301/1.4404 (304/316L)

Gasket: EPDM-FDA listed

Measuring system

Sensor: Piezoresistive Thin film

Sensor filling: Synthetic oil, free of

silicone FD1, FDA listed without

Accuracy

General:

Limit point

setting: per DIN 16086

Reference

conditions: per EN 60770-1

Linearity

errors: 0.15 % of span

TD 5:1 no modification

Hysteresis: 0.05 % of nominal range

Repeatability: 0.05 % of nominal range

Calibration

position: Vertical mounting position

Influence of

mounting position: 3.5 mbar

Data sheet D4-017-1 Rev. 1G5

Long-term drift:

(EN 60770-1) 0.1 % / year of nominal range

Temperature

effect: Case:

Lower range value / upper range value

Range 0...60 °C:

± 0.15 % / 10K of nominal range

Range < 0 °C, > 60 °C:

± 0.2 % / 10K of nominal range

Output

General:

Delay time: approx. 160 ms

Measuring cycle: 6 measurements / second

Measuring range

setting: Turndown 5:1

Basic module: 4...20 mA

Signal: 4...20 mA, 2-wire

Current range: 3.8...20.8 mA

Current limitation: approx. 22 mA

Alarm state: < 3.6 mA, optional > 21 mA

Damping: 0...120 seconds

Load R

B : R B (U V -12V DC)/0,022A [Ohm] U V = supply voltage

Basic module: PROFIBUS PA

Signal: digital per IEC 61158-2

Protocol: EN 50170-PROFIBUS PA, Profile 3.0

Sensor address: 0...126 (126 = factory setting)

Power consumption: constantly 11 mA

Fault current

I FDE