Mounting and Wiring Variable Air Volume Modular Assembly (VMA
Jan 7 2003 The damper actuator direction to close establishes upon installation of the VMA
MATHEMATICS
VABCD is a square-based pyramid. The horizontal base ABCD has side length 10 cm and centre M. Angle VMA is 90". Angle VAM is 68
Le calcul de la VMA – Vitesse Maximale Aérobie
La vitesse maximale aérobie ou VMA est la vitesse de course à partir de laquelle une personne consomme le maximum d'oxygène. En deçà de cette limite
TRANSFER PLANNING WORKSHEET BUNKER HILL COMMUNITY
Academic Majors within the College of Science and Math. • Biochemistry. • Biology VMA-225. Painting Concepts. 3. TRANSFER PLANNING WORKSHEET.
vSphere Management Assistant Guide - OpenTopic
Administrators can use the vSphere Management Assistant automated authentication facilities and the software packaged with vMA to interact with ESXi hosts and
Superpave Volumetric Calculations Review
%VMA = Percent Voids in Mineral Aggregate. Pa = Percent of Air Voids. Example Calculation: %VMA = 12.4%. Pa = 5.3. % = 100 × . 12.4 ? 5.3.
Closed-form results for vector moving average models with a
May 1 2020 The estimation of a vector moving average (VMA) process represents a challenging ... Society for Industrial and Applied Mathematics.
5.10.4. CALCULATIONS FOR THE MARSHALL MIX DESIGN OF
Calculate the effective asphalt content of the mixture. (Pbe). 2.9. Calculate the percent voids in the mineral aggregate in the compacted paving mixture. (VMA).
Your Ref:
Sep 1 2020 3:10 4:10pm Maths. 11.1 Maths /MMO/S1. 11.2 Maths/VMA/S2. 11.3 Maths /SAB/S16. 11.4 Maths/MTA/S17. 11.5 Maths/HCH/F15. English.
Applications of the Periodogram Method for Perturbed Block Toeplitz
Apr 14 2020 Our parameter estimation method for perturbed VMA processes is ... Rudin
Technical Bulletin
Issue Date January 7, 2003
© 2003 Johnson Controls, Inc. www.johnsoncontrols.com Code No. LIT-6363125Mounting and Wiring Variable Air Volume ModularAssembly (VMA) 1400 Series Controllers
Mounting and Wiring VMA1400 Series Controllers............................3Introduction......................................................................................................... 3
Key Concepts...................................................................................................... 4
VMA Position and Orientation...........................................................................................4
Damper Actuator Direction to Close..................................................................................4
N2 Address Switches........................................................................................................4
Wiring and Cabling Precautions........................................................................................5
General Wiring Information ...............................................................................................6
Power Source Wiring ........................................................................................................6
Phone Jack Polarization..................................................................................................10
Sensor Interfaces............................................................................................................11
Procedure Overview......................................................................................... 14
Detailed Procedures......................................................................................... 16
Preparing the VMA for Mounting.....................................................................................16
Mounting the VMA1410/1420..........................................................................................18
Mounting the VMA1430...................................................................................................19
Setting the Damper Position (VMA1410, 1420, or VMA1430 with External Actuator) ....19Wiring the VMA ...............................................................................................................21
Connecting the N2 Bus ...................................................................................................24
Reference Information ..................................................................................... 26
VMA Wiring List...............................................................................................................26
VMA Single Duct Application Wiring Diagram.................................................................28
VMA Single Duct Supply/Exhaust Wiring Diagram .........................................................29
VMA Dual Duct Application Wiring Diagram ...................................................................30
VMA Internal Schematic Diagram...................................................................................32
Fabricating Your Own Interconnection Cable .................................................................34
Troubleshooting............................................................................................... 35
Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin2
Troubleshooting VMA Room Temperature Drift..............................................................35
Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin3
Mounting and Wiring VMA1400
Series Controllers
Introduction
The integrated VMA1410/1420, which includes a controller, actuator, and pressure sensor, mounts on the Variable Air Volume (VAV) terminal box. The VMA1430 mounts anywhere on the VAV box and is wired to a separate damper actuator. Note: This document focuses on the VMA1410, 1420, and1430 controllers. The VMA1400 Series also includes the VMA1440,
which is a controller used exclusively as part of the Metasys® Zoning Package. See the Metasys Zoning Package Product Bulletin (LIT-639050) and the Metasys Zoning Package Overview Technical Bulletin (LIT-639100) for information on this specialized product. Instructions for wiring the VAV Modular Assembly (VMA) and its accessory devices are provided in this section.This document describes how to:
prepare the VMA for mounting mount the VMA1410/1420 mount the VMA1430 set the damper position (VMA1410, 1420, or VMA1430 with external actuator) wire the VMA connect the N2 Bus Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin4
Key Concepts
VMA Position and Orientation
Consider the following when positioning and orienting the VMA: Mount the VMA on a vertical and flat surface where it functions best, such as the side of the VAV box. Route or loop the tubing, so a portion of it is lower than the pressure sensor, to create a moisture trap that prevents any condensation from entering the sensor. Do not make any sharp bends in the tubing, as this could collapse the tube and block the pressure path.Verify wiring terminals are accessible.
Ensure that no extra mounting brackets, linkage, or couplers are required for standard mounting. Locate the VMA so that it has adequate clearance for future servicing and is protected from moisture and corrosive fumes.Damper Actuator Direction to Close
The damper actuator direction to close establishes upon installation of the VMA, using HVAC PRO software. The damper must be manually positioned to allow the VMA actuator to fully open and close the damper. Incorrect damper positions in a zone can lead to misdiagnosed readings, resulting in unnecessary repetition of setup and diagnostics.N2 Address Switches
It is best, from an accessibility standpoint, to set the N2 switches before mounting the VMA. The switches, located on the side of the VMA, are set to On for the address numbers indicated on the room schedule or building drawings. Use Addresses 1-253 only. Addresses 0, 254, and 255 are reserved. Refer to the Preparing the VMA for Mounting section in this document for further information. If software addressing is used, N2 switches must be set to 0 or 255. See the HVAC PRO User's Guide for details on software addressing. Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin5
Wiring and Cabling Precautions
WARNING: Risk of Electrical Shock or Equipment Damage. To avoid damaging equipment or possible electrical shock, ensure that all power supplies to the system are disconnected prior to wiring.CAUTION: Risk of Equipment Damage.
Shorting of Binary Outputs (BOs) while energized will destroy the VMA output triac. Read these precautions before touching the terminals or wiring theVMA and its accessories:
Make all wiring connections in accordance with the National Electrical Code (NEC) and state and local regulations. For transformer primaries above 150 VAC, the secondary must be earth grounded at the transformer to meet NEC. Terminal 1 can be earth grounded. Grounding on Terminal 1 results in 24 VAC being applied to DCOM with respect to earth. Note: 24 VAC to 24 VAC isolation transformers are not necessary. The power supply is internally isolated. For specific methods for wiring the VMA to meet UL 864 requirements, refer to the Metasys Smoke Control Wiring Technical Bulletin (LIT-636331). Terminal 3 is an earth ground connection (optional). Locate equipment and route the wiring so that twisted pair signal wiring is separated from power wiring by at least 150 mm (6 in.). Make all wiring connections to the VMA using only copper conductors. To establish tight, reliable electrical connections, use the correct wire sizes for the terminals. Avoid very thin solid wires, such as 26 AWG or less than 0.6 mm, which tend to break. Daisy chain the N2 Bus. The use of Y or T connections without a repeater installed as the T-tap may cause a loss of communications. Make sure that there is at least one End-of-Line termination on the N2 Bus (usually at the Network Control Module [NCM] or N30). Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin6
Do not run N2 Bus, Zone Bus, Analog Input (AI), Binary Input (BI), Analog Output (AO), or Binary Output (BO) wiring in the same conduit as line voltage wiring (above 30 VAC), or with wiring that switches power to highly inductive loads such as contactors, coils, motors, or generators. Run Zone Bus, AI, AO, and BI wiring in the same bundle or conduit where convenient. If the BO wiring is not wired through other switches or contacts, such as actuator end-of-travel switches, bundle it with the other Input/Output (I/O) wiring where convenient.General Wiring Information
The following are general wiring considerations:
The VMA includes isolated N2, isolated binary outputs, and isolated 24 VAC. The 24 VAC power input is internally transformer isolated by the VMA. To meet NEC requirements for line voltage greater than150 VAC, Terminal 1 can be earth grounded.
Up to ten cooling-only controllers (VMA1410) can be powered from one 100 VA low-voltage, power-limited, Class 2 transformer. See Power Source Wiring below for more information. Conduit is not required by the NEC for Class 2 wiring installations. Large insulated spade lugs with a polarizing tab (for high voltage) do not fit on the VMA.Power Source Wiring
To calculate the number of VMAs that can be powered from one 100 VA unit, use the equation below. In this equation, the value Total VA equals the total VA consumed by the VMA, actuator, and output loads.VATotal100 r TransformeVA 100per VMAs
Table 1 shows the power rating for each cooling/heating coil valve actuator. The valve power plus the VMA power (1410/1420 = 10 VA;1430 = 3 VA) must not exceed 100 VA. If a device is not listed in
Table 1, refer to the product literature for that device. Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin7
Table 1: Actuator VA Power Rating
Actuator Type Power Rating
VA-8020Incremental 4 VA
VA-8050Incremental 6 VA
VA-7150Incremental 2.7 VA
VA-7153Incremental w/feedback 2.7 VA
JS/JT Series Electric Zone
ValveOn/Off 7 VA
JM Series Electric Zone
Valve with JT Series
ActuatorIncremental 1.2 VA
JM Series Electric Zone
Valve with JP Series
ActuatorVoltage (0 to 10 VDC) 1.6 VA
VA-8122Voltage (0 to 10 VDC) 4 VA
VA-7152Voltage (0 to 10 VDC) 4.7 VA
VA-7200Incremental 6.7 VA
VA-7203Incremental w/feedback 6.7 VA
VA-7202Voltage (0 to 10 VDC) 8.7 VA
GE RR-7 or TouchplateLighting relay 42 VA for 50 ms*VA-7450Incremental 2.5 VA
VA-7452Voltage (0 to 10 VDC) 2.5 VA
VA-7040Thermal (DAO) 3 VA
VA-7310Incremental 2 VA
VA-7312Voltage (0 to 10 VDC) 2 VA
VA-7010On/Off 7 VA
VA-4233-BGA-2On/Off, Spring Return 12 VA
VA-4233-AGA-2Incremental, Spring Return 12 VA
VA-4233-GGA-2Voltage (0 to 10 VDC),
Spring Return12 VA
M9106-AGA-2Incremental 2.5 VA
M9106-GGA-2Voltage (0 to 10 VDC) 3.2 VA
M9206-BGA-2On/Off, Spring Return 16 VA
M9206-AGA-2Incremental, Spring Return 16 VA
M9206-GGA-2Voltage (0 to 10 VDC),
Spring Return16 VA
M9104-AGA-2NIncremental 3.4 VA
M9104-AGA-2Incremental w/conduit 3.4 VA
M9104-AGS-2NIncremental w/DPT-2015 3.4 VA
M9104-GGA-2Proportional 0-10 V 5 VA
M9104-GGC-2Proportional 0-10 V
w/conduit5 VA * Do not schedule all lights on one transformer to turn on at the same time. The current surge on the transformer could open the circuit breaker. Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin8
When using a single transformer to power multiple VMAs, use a wire gauge large enough to handle the current and minimize the voltage drop. The voltage drop depends on the current draw, wire gauge, and wire length. On a fully loaded 100 VA transformer, a 120 VAC primary draws only 0.8 amperes, while the 24 VAC secondary draws4 amperes.
The standard 2.5 mm
2 (14 AWG) cable (Example 1 in Figure 1) is limited to 27 m (88 ft) with ten cooling-only VMAs, all at one end of the cable. If the transformer is centered (Example 2 in Figure 1) with five VMAs on the left and five VMAs on the right, the distance in each direction can be increased. This is because both the current and voltage drop are halved. In this example, both the left and the right legs could be increased to 54 m (176 ft) from the transformer (50 VA from each leg), creating a 108 m (352 ft) total length. < 88 ft of 14 AWG >24 VAC
< 176 ft of 14 AWG > < 176 ft of 14 AWG >100 VA24 VAC
100 VA
VMAVMAVMAVMAVMAVMAVMA
VMAVMAVMA
VMAVMA
VMAVMA
Example 1: All ten VMAs are at one end.
Example 2: Transformer is centered.
VMAVMA
VMA VMAVMAVMA
Cable_lg
Figure 1: Power Cable Lengths
There are two ways to connect power and loads to the VMA.Individual spade lugs accept a single 4 mm
2 to 0.8 mm (10 to 22 AWG) wire and fit on 6 mm (1/4 in.) tabs, or optional screw terminals can be assembled over the spade lugs. The screw terminals accept up to a single 4 mm 2 (12 AWG) wire or two 2.5 mm 2 (14 AWG) wires. When two wires are crimped into one spade lug, a wire nut (to connect two heavy wires to a short 152 mm [6 in.] thinner wire) or a larger spade lug barrel is needed. Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin9
The following tables indicate the relationship between cable length and power at the end of wires. Table 2: Maximum 24 VAC Secondary Cable Length for Given Power/Gauge (U.S. Measurements)Cable Size
8 Gauge 10 Gauge 12 Gauge 14 Gauge 16 Gauge 18 Gauge
Power (VA) at
End of Wire Cable Length (ft)
103520 2200 1400 880 550 350
201760 1110 700 440 275 175
301173 740 467 293 183 117
40880 555 350 220 138 88
50704 444 280 176 110 70
60587 370 233 147 92 58
70503 317 200 126 79 50
80440 278 175 110 69 44
90391 247 156 98 61 39
100352 222 140 88 55 35
Table 3: Maximum 24 VAC Secondary Cable Length for Power/WireGauge (Metric Measurements)
Cable Size
4 mm 22.5 mm
21.5 mm
2Power (VA) at
End of Wire Cable Length (Meters)
10427 268 168
20213 134 84
30142 89 56
40107 67 42
5085 54 34
6071 45 28
7061 38 24
8053 34 21
9048 30 19
10043 27 17
Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin10
Phone Jack Polarization
Figure 2 illustrates the polarization of the 6-pin and 8-pin phone jacks on the VMA or room sensor (TE-6700 or TMZ1600). Pin 1 is to the extreme left as you face the jack opening, tab notch down. Note: If you need to create your own cable, refer to FabricatingYour Own Interconnection Cable
in the Reference Information section of this document. Otherwise, order pre-terminated cables.8-pin 6-pinVMA
Room Sensor
phonejac Pin 1Figure 2: Phone Jack Polarization
Table 4: TE-6700 Phone Jack Pin Identification
8-Pin Phone Jack on VMA 6-Pin Phone Jack on TE-6700
Pin Signal Pin Signal
1BI-1 Temp Occ1Not used
2AI 2 Zone Setpoint2+15 VDC
3AI 1 Temperature Sensor3COM
4COM for AI-14Not used
5+15 VDC5Zone Bus (ZB)
6ZB COM/LED BI COM6Not used
7COM for AI-2
8ZB+Table 5: TMZ Phone Jack Pin Identification
8-Pin Phone Jack on TMZ 6-Pin Phone Jack on TMZ
Pin Signal Pin Signal
1Not used1Not used
2Not used2+15 VDC
3AI1, Zone Temperature Sensor3COM
4AI1, Sensor Common4Not used
5+15 VDC5Zone Bus (ZB)
6Supply/Zone Bus Common6Not used
7Not used
8Zone Bus
Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin11
Sensor Interfaces
Figures 3, 4, and 5 show interfaces between room sensors and the VMA. For more information on the TE-6700 room sensor (includingDIP switch settings), see the
TE-6700 Series 2nd Generation
Temperature Elements Installation Bulletin (LIT-216332) CAUTION:Intermittent connections can occur when small gauge solid wire is crimped into large spade lugs or a when a phone jack is poorly crimped. Any of the following situations can cause AI drifting:26 gauge solid wire is crimped in a 18-22 gauge stranded spade
connector.Phone jack is poorly crimped.
Pliers or something other than crimping tool is used to crimp the spade lug. Paint or other material is on phone jack connector.See the
Troubleshooting section for more information.
1 2 3 4 5 6 7 8 1 2 3 4 5 6 BI-1AI-2 (Setpoint)
AI-1 (Zone Temperature)
AI-1 COM
+15 Volts DC +15/Zone Bus COM (Not BCOM)AI-2 COM
Zone Bus/N3+Sensor
1.6 K ohm
Setpoint Potentiometer
6-pin Phone Jack
on TE-6700 +15 Volts DCZone Bus
COM8-pin Phone Jack
on TE-6700ScrewTerminals
TE6X 4 1 2 5 6 3 7LED*Manual
Override
1 K ohm
8Preferred DIP Switch
Position for TE-6700 (LED On)
O N1 2 3
Figure 3: TE-6700 Phone Jack Interface to VMA
Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series ControllersTechnical Bulletin12
1 845AI1 AI COMAI COM AI2quotesdbs_dbs47.pdfusesText_47
[PDF] Maths, abscisse, ordonné, repère orthonormé
[PDF] Maths, antécédents d'un nombre
[PDF] Maths, besoin d'aide
[PDF] Maths, Calcule litérral,Développement et Factorisation! Aider moi SVP!
[PDF] Maths, calculs de volumes et problème
[PDF] Maths, demi cercle,triangle,cosinus,nombre dérivé
[PDF] Maths, devoir maison
[PDF] Maths, DM sur les fonctions
[PDF] maths, dm sur pavé
[PDF] Maths, Exercice sur la borne kilométrique, valeur de x
[PDF] Maths, exercice sur la sécurité routière
[PDF] MATHS, livre phare 3éme
[PDF] Maths, muliplication nb relatifs ! HELP !
[PDF] maths, triplets pythagoriciens